MODEL |
TLEVP10-RT
|
TLEVP15-RT |
TLEVP20-RT
|
Capacity (VA/Watts) |
10k/10k
|
15k/15k |
20k/20k
|
INPUT |
Nominal Voltage |
380/400/415 (3Ph+N+PE)
|
Operating voltage range |
138~485Vac for 40%load; 305~485Vac for full-load
|
Operating frequency range |
40~70Hz
|
Power Factor |
≥0.99
|
Harmonic distortion (THDi) |
≤3% (100% linear load)
|
Bypass input |
Bypass voltage range |
Max. voltage:220V: +25%(optional +10%,+15%,+20% ) ;
230V: +20%(optional +10%,+15% ) ;
240V: +15%(optional +10%)
Min. voltage: -45% (optional -10%,-20%,-30%)
|
Bypass Frequency range |
Frequency protection range: ±10%
|
Generator input |
Support
|
OUTPUT |
Output Voltage |
380/400/415Vac,(3Ph+N+PE)
|
Power Factor |
1.0
|
Output frequency(Hz) |
Line mode:Synchronize with input ;when input frequency >±10%%(±1%、±2%、±4%、±5% Optional,
Output frequency 50×(1±0.1%)Hz Battery mode :(50/60±0.1%)Hz
|
Waveform |
Pure sine wave
|
Crest factor |
3:1
|
Harmonic distortion(THDV) |
≤2%(100% linear load); ≤4% (100% non linear load)
|
Transfer Time(ms) |
0 Ms
|
Efficiency |
UP to 95
|
Overload |
≤110% overload for 60 min; 125% overload for 10 min; ≤150% overload for 1 min
|
Bypass Mode |
135% overload for long term; >1000% overload for 100 ms
|
BATTERY |
Battery Voltage |
For optional : Optional Voltage: ±180/192/204/216/228/
240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/
46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 30 pcs default, 36~50 pcs fully output ; 32~34 pcs
Out put power factor 0.9; 30 pcs output power factor 0.8;)
|
Max charger current (A) |
18
|
20
|
Others |
Alarm function |
Overload、utility abnormal、UPS fail、battery low voltage etc
|
Protection function |
Short circuit、overload、overheat、battery low、output low voltage、fan fault、Anti-thunder
|
SYSTEM FEATURES |
Overload |
Line Mode |
Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, ≥150% turn to bypass mode immediately
|
Bat. Mode |
Load≤110%: last 10min, ≤125%: last 1min, ≤150%: last 5S, ≥150% shut down UPS immediately
|
Bypass Mode<40℃<=”” style=”box-sizing: border-box;”> |
Breaker( Load < 125%, long-term operation)
|
Short circuit |
Hold whole system
|
Communication interface |
RS232, RS485, Parallel, Intelligent Slot(SNMP card/ Relay card(optional)),
BMS (optional),EPO port, Output port, MAINTAIN-AUXSWS
|
PHYSICAL |
Dimension W×H×D (mm) |
443×131(3U)x580 mm
|
Net Weight (kg) |
29
|
31 |
32
|
ENVIRONMENT |
Operating temperature |
0~40℃
|
Storage temperature |
-25℃~60℃
|
Humidity range |
0~95% (non-condensing)
|
Altitude |
<1500m(when excess 1500m, according to GB/T 3859.2 to derating)
|
Noise Level |
<55db
|
STANDARDS |
Safety |
IEC/EN62040-1,IEC/EN60950-1
|
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
|