Notice: Function _load_textdomain_just_in_time was called incorrectly. Translation loading for the premium-addons-for-elementor domain was triggered too early. This is usually an indicator for some code in the plugin or theme running too early. Translations should be loaded at the init action or later. Please see Debugging in WordPress for more information. (This message was added in version 6.7.0.) in /home/u800375974/domains/technoline-ca.com/public_html/wp-includes/functions.php on line 6114
EVP PLUS T3 30.0 – Technoline

EVP PLUS T3 30.0

EVP PLUS T3 30.0

Part Number :TLEVP30

Desciption:

  • Complete protection from blackout, voltage fluctuations (overvoltages and undervoltages), lightning (with upstream arrester), frequency variations, surge, harmonics, voltage distortions
  • Recommended for Local Area Networks (LAN), Data Centers, Industry, Electromedical Equipments
  • Intelligent slot for SNMP, Dry Contact or MODBUS card
  • On-Line Double Conversion technology transformerless (VFI-SS-111)
  • Active PFC circuit (0.99)
  • Compatibility with generator
  • Static and manual bypass
  • Frequency converter mode
MODEL

TLEVP10

TLEVP15 TLEVP20

TLEVP30

Capacity (VA/Watts)

10k / 9k

15k / 13.5k 10k / 18k

30k / 27k

INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 138~485Vac for 40%load; 305~485Vac for full-load
Operating frequency range 40~70Hz
Power factor ≥0.99
Bypass voltage range 220Vac Max.voltage: +25%(optional +10%,+15%,+20% )
230Vac Max.voltage: +20%(optional +10%,+15% )
240Vac Max.voltage: +15%(optional +10% )
Min. voltage: -45% (optional -20%,-30%)
Frequency synchronize tracing range: ±10%
generator input Support
Harmonic distortion (THDi) ≤3%(100% non-linear load)
OUTPUT
Rated voltage 380/400/415Vac(3Ph+N+PE)
Power factor 0.9
Voltage
regulation
±1%
Frequency Line mode synchronize with input; when input frequency >±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz
Bat. mode 50/60(±0.1)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤2% with linear load
≤4% with non-linear load
Efficiency 96%
BATTERY
Battery voltage ±96/108/120Vdc; battery quantity (16~20 pcs, 16 pcs define, Standard unit and 20 pcs no power derating; 18 pcs output power factor 0.8/0.9; 16 pcs output power factor 0.7/0.8;)
Charging current
(A)(Charging current can be set according to battery capacity installed)
 14A (Max.)  16A (Max.)  18A (Max.)  20A (Max.)
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload ≤110% overload 60 min; ≤150% overload 1 min,to Bypass
Bypass mode:135% overload long time; >1000% overload 100 ms
 Backfeed protection Support
Alarm Overload, utility abnormal, UPS fault, battery low, etc.
Protection Short circuit, overload, over temperature, battery low, fan fault alarm.
 Remote LCD Support
Communication
interface
USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional)
ENVIRONMENT
Operating temperature 0~40℃
Storage
temperature
25~55℃(No battery)
Humidity range 0~95% (Non-condensing)
Altitude <1500m. When >1500m, derating power for use
Noise level <55db <58dB  <61dB
PHYSICAL
Dimension
D×W×H (mm)
828×250×868
Net weight (kg) 57 63 64 71
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8