MODEL |
TLEVP10
|
TLEVP15 |
TLEVP20 |
TLEVP30
|
Capacity (VA/Watts) |
10k / 9k
|
15k / 13.5k |
10k / 18k |
30k / 27k
|
INPUT |
Nominal voltage |
380/400/415Vac, (3Ph+N+PE) |
Operating voltage range |
138~485Vac for 40%load; 305~485Vac for full-load |
Operating frequency range |
40~70Hz |
Power factor |
≥0.99 |
Bypass voltage range |
220Vac Max.voltage: +25%(optional +10%,+15%,+20% )
230Vac Max.voltage: +20%(optional +10%,+15% )
240Vac Max.voltage: +15%(optional +10% )
Min. voltage: -45% (optional -20%,-30%)
Frequency synchronize tracing range: ±10% |
generator input |
Support |
Harmonic distortion (THDi) |
≤3%(100% non-linear load) |
OUTPUT |
Rated voltage |
380/400/415Vac(3Ph+N+PE) |
Power factor |
0.9 |
Voltage
regulation |
±1% |
Frequency |
Line mode |
synchronize with input; when input frequency >±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz |
Bat. mode |
50/60(±0.1)Hz |
Crest factor |
3:1 |
Harmonic distortion (THDv) |
≤2% with linear load
≤4% with non-linear load |
Efficiency |
96% |
BATTERY |
Battery voltage |
±96/108/120Vdc; battery quantity (16~20 pcs, 16 pcs define, Standard unit and 20 pcs no power derating; 18 pcs output power factor 0.8/0.9; 16 pcs output power factor 0.7/0.8;) |
Charging current
(A)(Charging current can be set according to battery capacity installed) |
14A (Max.) |
16A (Max.) |
18A (Max.) |
20A (Max.) |
SYSTEM FEATURES |
Transfer time |
Utility to Battery : 0ms; Utility to bypass: 0ms |
Overload |
≤110% overload 60 min; ≤150% overload 1 min,to Bypass
Bypass mode:135% overload long time; >1000% overload 100 ms |
Backfeed protection |
Support |
Alarm |
Overload, utility abnormal, UPS fault, battery low, etc. |
Protection |
Short circuit, overload, over temperature, battery low, fan fault alarm. |
Remote LCD |
Support |
Communication
interface |
USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional) |
ENVIRONMENT |
Operating temperature |
0~40℃ |
Storage
temperature |
25~55℃(No battery) |
Humidity range |
0~95% (Non-condensing) |
Altitude |
<1500m. When >1500m, derating power for use |
Noise level |
<55db |
<58dB |
<61dB |
PHYSICAL |
Dimension
D×W×H (mm) |
828×250×868 |
Net weight (kg) |
57 |
63 |
64 |
71 |
STANDARDS |
Safety |
IEC/EN62040-1,IEC/EN60950-1 |
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |