MODEL |
TLEVD10-RT |
TLEVD15-RT |
TLEVD20-RT |
Capacity (VA/Watts) |
10k/10k |
15k/15k |
20k/20k |
INPUT |
Nominal Voltage |
380/400/415 (3Ph+N+PE) |
Operating voltage range |
138~485Vac for 40%load; 305~485Vac for full-load |
Operating frequency range |
40~70Hz |
Power Factor |
≥0.99 |
Harmonic distortion (THDi) |
≤3% (100% linear load) |
Bypass input |
Bypass voltage range |
Max. voltage:220V: +25%(optional +10%,+15%,+20% ) ;
230V: +20%(optional +10%,+15% ) ;
240V: +15%(optional +10%)
Min. voltage: -45% (optional -10%,-20%,-30%) |
Bypass Frequency range |
Frequency protection range: ±10% |
Generator input |
Support |
OUTPUT |
Output Voltage |
220/230/240Vac,(P-N) |
Power Factor |
1.0 |
Output frequency(Hz) |
Line mode:Synchronize with input ;when input frequency >±10%%(±1%、±2%、±4%、±5% Optional,
Output frequency 50×(1±0.1%)Hz Battery mode :(50/60±0.1%)Hz |
Waveform |
Pure sine wave |
Crest factor |
3:1 |
Harmonic distortion(THDV) |
≤2%(100% linear load); ≤4% (100% non linear load) |
Transfer Time(ms) |
0 Ms |
Efficiency |
UP to 95 |
Overload |
≤110% overload for 60 min; 125% overload for 10 min; ≤150% overload for 1 min |
Bypass Mode |
135% overload for long term; >1000% overload for 100 ms |
BATTERY |
Battery Voltage |
For optional : Optional Voltage: ±180/192/204/216/228/
240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/
46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 30 pcs default, 36~50 pcs fully output ; 32~34 pcs
Out put power factor 0.9; 30 pcs output power factor 0.8;) |
Max charger current (A) |
18 |
20 |
Others |
Alarm function |
Overload、utility abnormal、UPS fail、battery low voltage etc |
Protection function |
Short circuit、overload、overheat、battery low、output low voltage、fan fault、Anti-thunder |
SYSTEM FEATURES |
Overload |
Line Mode |
Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, ≥150% turn to bypass mode immediately |
Bat. Mode |
Load≤110%: last 10min, ≤125%: last 1min, ≤150%: last 5S, ≥150% shut down UPS immediately |
Bypass Mode<40℃<=”” style=”box-sizing: border-box;”> |
Breaker( Load < 125%, long-term operation) |
Short circuit |
Hold whole system |
Communication interface |
RS232, RS485, Parallel, Intelligent Slot(SNMP card/ Relay card(optional)),
BMS (optional),EPO port, Output port, MAINTAIN-AUXSWS |
PHYSICAL |
Dimension W×H×D (mm) |
443×131(3U)x580 mm |
Net Weight (kg) |
29 |
31 |
32 |
ENVIRONMENT |
Operating temperature |
0~40℃ |
Storage temperature |
-25℃~60℃ |
Humidity range |
0~95% (non-condensing) |
Altitude |
<1500m(when excess 1500m, according to GB/T 3859.2 to derating) |
Noise Level |
<55db |
STANDARDS |
Safety |
IEC/EN62040-1,IEC/EN60950-1 |
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |