EVD PLUS T1 15.0

EVD PLUS T1 15.0

Part Number :TLEVD15

Desciption:

  • Complete protection from blackout, voltage fluctuations (overvoltages and undervoltages), lightning (with upstream arrester), frequency variations, surge, harmonics, voltage distortions
  • Recommended for Local Area Networks (LAN), Data Centers, Industry, Electromedical Equipments
  • Power factor 1
  • LCD Touch graphic display
  • Double input mains/bypass
  • Intelligent slot for SNMP, Dry Contact or MODBUS card
  • On-Line Double Conversion technology transformerless (VFI-SS-111)
  • Active PFC circuit (0.99)
  • Compatibility with generator
  • Static and manual bypass
  • Frequency converter mode
MODEL

TLEVD10

TLEVD15 TLEVD20

TLEVD30

Capacity (VA/Watts)

10k / 9k

15k / 13.5k 20k / 18k

30k / 27k

INPUT
Operating frequency range

40~70Hz

Power factor

≥0.99

Bypass voltage range

220Vac Max.voltage: +25%(optional +10%,+15%,+20% )
230Vac Max.voltage: +20%(optional +10%,+15% )
240Vac Max.voltage: +15%(optional +10% )
Min. voltage: -45% (optional -20%,-30%)
Frequency synchronize tracing range: ±10%

generator input

Support

Harmonic distortion (THDi)

≤3%(100% non-linear load)

OUTPUT
Rated voltage

220/230/240Vac,(P-N)

Power factor

0.9

Voltage
regulation

±1%

Frequency Line mode

synchronize with input; when input frequency >±10% (±1%/±2%/±4%/±5% optional), output (50/60±0.1)Hz

Bat. mode

50/60(±0.1)Hz

Crest factor

3:1

Harmonic distortion (THDv)

≤2% with linear load
≤4% with non-linear load

Efficiency

96%

BATTERY
Battery voltage

±96/108/120Vdc; battery quantity (16~20 pcs, 16 pcs define, Standard unit and 20 pcs no power derating; 18 pcs output power factor 0.8/0.9; 16 pcs output power factor 0.7/0.8;)

Charging current
(A)(Charging current can be set according to battery capacity installed)

 14A (Max.)

 16A (Max.)  18A (Max.)

 20A (Max.)

SYSTEM FEATURES
Transfer time

Utility to Battery : 0ms; Utility to bypass: 0ms

Overload

≤110% overload 60 min; ≤150% overload 1 min,to Bypass
Bypass mode:135% overload long time; >1000% overload 100 ms

 Backfeed protection

Support

Alarm

Overload, utility abnormal, UPS fault, battery low, etc.

Protection

Short circuit, overload, over temperature, battery low, fan fault alarm.

 Remote LCD

Support

Communication
interface

USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional)

ENVIRONMENT
Operating temperature

0~40℃

Storage
temperature

25~55℃(No battery)

Humidity range

0~95% (Non-condensing)

Altitude

<1500m. When >1500m, derating power for use

Noise level

<55db

<58dB

 <61dB

PHYSICAL
Dimension
D×W×H (mm)

828×250×868

Net weight (kg)

57

63 64

71

STANDARDS
Safety

IEC/EN62040-1,IEC/EN60950-1

EMC

IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8