MODEL |
EVD6RT-MM
|
EVD10RT-MM
|
Capacity |
6000VA/ 5400W
|
10000VA/ 9000W
|
INPUT |
|
Nominal voltage |
208/220/230/240Vac
|
Input voltage range |
110~286Vac
|
Frequency range |
40~70Hz (50/60Hz Auto-Sensing)
|
Power factor |
≥0.99
|
|
Max.voltage:220V:+25% (Optional+10%,+15%,+20%) 230V:+20% (Optional+10%,+15%,+20%)
|
Bypass voltage range |
240V:+15% (Optional+10%)
|
|
Min.voltage:-45% (Optional-20%,-30%)
|
OUTPUT |
|
Output voltage |
208/220/230/240Vac
|
Power factor |
0.9
|
Voltage regulation |
±1%
|
Output frequency |
Line Mode |
±1%/±2%±/±4%/±5%/±10% of the rated frequency (Optional)
|
Bat. Mode |
(50/60±0.1%)Hz
|
Crest factor |
3:01
|
Harmonic distortion (THDv) |
≤2% Linear load
|
≤5% Non linear load
|
Transfer time |
AC mode to Bat.Mode |
0ms
|
Inverter to Bypass |
0ms
|
Output waveform |
Pure Sinewave
|
Overload |
Line Mode |
Load≤110% last 60min; ≤125% last 10min; ≤150% last 1min; >150% turn to bypass mode immediately
|
Bypass Mode |
40A (Breaker)
|
63A (Breaker)
|
fficiency |
94%
|
BATTERY |
|
Battery voltage |
±96/±108/±120Vdc (Adjustable)
|
Capacity (Standard unit) |
9Ah/12V (7Ah/12V optional)
|
Typical recharging time |
6~8 hours (to 90% of full capacity)
|
Charging current |
1A (Standard unit); Long run unit Max.current 10A (Charging current can be set according to battery capacity)
|
INDICATORS |
|
LED display |
Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
|
LCD display |
Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,
|
Battery voltage,Inner temperature& Remaining battery backup time
|
ALARM |
|
Battery mode |
Beeping every 4 seconds
|
Battery low |
Beeping every second
|
Overload |
Beeping twice every second
|
Fault |
Continously beeping
|
PHYSICAL |
|
Dimension W x D×H (mm) |
440 x 625 x 86.5
|
Net weight (kg) |
16
|
18
|
ENVIRONMENT |
|
Operating temperature |
0℃~40℃
|
Storage temperature |
-25℃~55℃
|
Humidity range |
20~95%RH @ 0~40℃ (Non condensing)
|
Altitude |
<1500m,derating required when>1500m
|
Noise level |
<55db at 1 Meter
|
<58db at 1 Meter
|
STANDARDS |
|
Safety |
IEC/EN62040-1,IEC/EN62477-1
|
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
|